Temperature Guide
Welcome to your new room! In order to accommodate your room temperature needs and comfort, each on-campus housing option has adjustable thermostat controls within the building. Please refer to the information presented below to properly control the temperature for your respective housing location. Proper handling of the temperature controls for your room is essential to conserve energy on campus, help the environment, and prevent unnecessary maintenance requests. If you have followed the directions as written, but are still experiencing issues with your room’s temperature, please contact our Facilities staff by submitting a maintenance request.
Visit the Stetson Energy and Water Conversation Policy and learn more about our climate commitment.
- Use up/down arrow to select desired set point
- Occupants Can Raise/Lower the Standard Temperature Setpoint +/- 2°F
*Setting Temperature beyond setpoint standards may damage the thermostat and will incur a fee of $250.
(Note: Setpoint Automatically Resets at 10:00 a.m. Each Day)

- Large Air Handlers Supply Each Wing/Pod (Both Floors) with Conditioned Air
- Airflow Volume is controlled at the Room Level by Automated Dampers
- Large Air Handlers Supply Conditioned Outside Air into the Hallways and Common Areas
- Each Room has an Individual Fan Coil Unit that Conditions the Air in that Space
- Campus-Wide Policy Setpoint Standards: Cooling 75°F / Heating 68°F
- Occupants Can Raise/Lower the Standard Temperature Setpoint +/- 2°F
(Note: Setpoint Automatically Resets at 10:00 a.m. Each Day)

- Large Air Handlers Supply Conditioned Outside Air into the Hallways and Common Areas
- Each Room has an Individual Fan Coil Unit that Conditions the Air in that Space
- Large Air Handlers Supply Conditioned Outside Air into the Hallways and Common Areas
- Each Room has an Individual Fan Coil Unit that Conditions the Air in that Space
- Campus-Wide Policy Setpoint Standards: Cooling 75°F / Heating 68°F
- Occupants Can Raise/Lower the Standard Temperature Setpoint +/- 2°F
(Note: Setpoint Automatically Resets 10:00 a.m. Each Day)

- Large Air Handlers Supply Conditioned Outside Air into the Hallways and Common Areas
- Each Room has an Individual Fan Coil Unit that Conditions the Air in that Space
- Large Air Handler Supplies Conditioned Outside Air into the Hallways and Common Areas
- Each Room has an Individual Fan Coil Unit that Conditions the Air in that Space
- Campus-Wide Policy Setpoint Standards: Cooling 75°F / Heating 68°F
- Occupants Can Raise/Lower the Standard Temperature Setpoint

- Large Air Handler Supplies Conditioned Outside Air into the Hallways and Common Areas
- Each Room has an Individual Fan Coil Unit that Conditions the Air in that Space
- One Air Handler Supplies Each Apartment (All Rooms) with Conditioned Air
- Airflow Volume is Controlled at the Room Level by Manual Vent Dampers
- Campus-Wide Policy Setpoint Standards: Cooling 75°F / Heating 68°F
- Occupants Can Raise/Lower the Standard Temperature Setpoint +/- 2°F
(Note: Setpoint Automatically Resets 10:00 a.m. Each Day)

- One Air Handler Supplies Each Apartment (All Rooms) with Conditioned Air
- Airflow Volume is Controlled at the Room Level by a Manual Vent Damper
- Large Air Handlers Supply Rooms and Common Areas with Conditioned Air
- Airflow Volume Controlled at the Room Level by Manual Vent Dampers
- Campus-Wide Policy Setpoint Standards: Cooling 75°F / Heating 68°F
- Temperature Regulated by the Return Air Average Temperature
(Note: Students who reside in these locations have no individual room thermostats)
- One Air Handler Supplies Each Apartment (All Rooms) with Conditioned Air
- Airflow Volume Controlled at the Room Level by Manual Vent Dampers
- Campus-Wide Policy Setpoint Standards: Cooling 75°F / Heating 68°F
- Occupants Can Raise/Lower the Standard Temperature Setpoint
- For Optimal Comfort, Keep the Fan Set to “Auto” and Temperature Within a Few Degrees of Standard
(Note: Setting the Temperature Too Low Can Cause the Unit to Freeze Up / Fail)

- One Air Handler Supplies Each Apartment (All Rooms) with Conditioned Air
- Airflow Volume is Controlled at the Room Level by Manual Vent Dampers
- One Air Handler Supplies Each Apartment (All Rooms) with Conditioned Air
- Airflow Volume is Controlled at the Room Level by Manual Vent Dampers
- Campus-Wide Policy Setpoint Standards: Cooling 75°F / Heating 68°F
- Occupants Can Raise/Lower the Standard Temperature Setpoint +/- 2°F
- For Optimal Comfort Keep the Fan Set to “Auto”
(Note: Setting the Temperature Too Low Can Cause the Unit to Freeze Up / Fail)

- One Air Handler Supplies Each Apartment (All Rooms) with Conditioned Air
- Airflow Volume is Controlled at the Room Level by Manual Vent Dampers
- Use the up/down arrow to select the desired set point
- Occupants Can Raise/Lower the Standard Temperature Setpoint +/- 2°F
*Setting Temperature beyond setpoint standards may damage the thermostat and will incur a fee of $250.
(Note: Setpoint Automatically Resets at 10:00 a.m. Each Day)

- Large Air Handlers supply each wing with conditioned air
- Airflow Volume is controlled at the Room Level by Automated Dampers
Temperature Control & Moisture Management
Managing temperature and airflow plays an important role in controlling moisture in your residential space. Because mold and mildew require moisture to grow, keeping your room’s HVAC system set and used correctly helps prevent conditions that allow moisture to linger.
Proper thermostat use, good airflow, and keeping vents unobstructed all support a healthy indoor environment. Following the temperature and ventilation guidance on this page helps your HVAC system function as designed and reduces excess humidity in your room.
For detailed information about mold, mildew, moisture prevention, cleaning expectations, health considerations, and how concerns are evaluated, visit our Mold, Mildew & Moisture Prevention resource.
Mold, Mildew and Moisture Prevention
When to Request Assistance
If you notice a moisture concern, visible growth that returns after cleaning, or conditions that seem unusual or persistent, submit a Maintenance Request so Facilities Management can evaluate the space and address any underlying issues.
Students who experience ongoing health symptoms should contact Student Health Service for guidance, as reactions to environmental allergens can vary.
Additional Resources
For general information about mold and indoor environments, you may also visit the CDC’s mold and moisture guidance.
